SCP-51D SCP-52D SCP-53D电路保护器Circuit Protectors
Type : SCP-D Type
▷ Din Rail Type ( SCP - D )
- 1 ~ 50A, 1 ~ 3 pole
- Breaking Capacity : AC 250V, 1.5kA
Ampere Frame | 50 | ||||
Type | SCP-51D | SCP-52D | SCP-53D | ||
Rating | Pole | 1 | 2 | 3 | |
Rated Current(ln) | 1 ,2, 3, 5, 7, 10, 15, 20, 25, 30, 34, 40, 45, 50 | ||||
Rated Operating Voltage(Ue) | AC(V) | 220 | 380 | ||
DC(V) | 80 | ||||
Operating Characteristics | Instantaneous(I), High(H), Middle(M), Low(L) | ||||
Rated Breaking Capacity(kA)(Sym) | AC 250V | 1.5kA (2.5kA) | |||
KSC8321, IEC60934, UL1077 | DC 80V | 1.5kA | |||
Number of Operating Cycles | Without Current | 35,000 | |||
With Current | 10,000 | ||||
Dimension (mm) | a | 19 | 38 | 57 | |
b | 67 | ||||
c | 65 | ||||
d | 71 | ||||
Weight(kg) | 0.12 | 0.24 | 0.36 | ||
Overcurrent Tripping method | Hydraulic-Magnetic method(HM) | ||||
Connection | DIN rail, Screw type | ||||
Internal Circuit | Series Trip | S | O | ||
Parallel Trip | P | ||||
Switch only | O | O | |||
Relay Trip | R | ||||
Accessories | Aux. Switch | W | O | ||
Alarm Switch | A | ||||
Voltage Trip | C | ||||
Aux. Contact Capacity | AC 250V 3A, DC 65V 3A |