model | mx2-v |
appearance(㎜) | 48(w)×96(h)×100(d) |
function | multi input, heating/cooling pid control, hba( heater break alarm ), remote function, manual output function, remote/local input se-lectable ℃/℉, reverse/direct action se-lectable. ramp |
power voltage | 110 ~ 240vac ( 50/60hz )
|
power consumption | max. 15va |
input | 11 kinds of input |
ct input | hba ( 25.0a or 50.0a ) |
control output | relay contact : ac 250v 5a ( resistive load ), ssr : 12v dc ( constant voltage pulse ) [ load resistance min. 800Ω ], current : 4 ~ 20ma dc ( load resistance max 600Ω ) |
control action | pid ( auto-tuning function ) or on/off |
alarm output | relay contact output : ac 250vac 3a ( al-2 ), 3a ( al-1 ) resistive load |
heater / loop break alarm | lba, hba [ relay contact output : ac 250, 3a ( resistive load )] |
setting | by up/down key on the front |
display | l.e.d display |
pv : 8 ㎜ , sv : 8 ㎜ |
setting and display accuracy | t/c : within ±3℃ ( 6℉ ) [ whichever is larger ] , r.input : 0 ~ 199℃ ( 0 ~ 399℃ ) within ±5℃ ( 10℉ ) , r.t.d : within ±2℃ ( 3℉ ) whichever is larger |
memory protection | semi-permanent |
sampling cycle | 500ms |
heating cycle | 1 ~ 100sec |
cooling cycle | 1 ~ 100sec |
cooling gain | display of 10 times to proportional band |
cooling deadband | -20.0 ~ 20.0℃ ( ℉ ) |
input correction range | slu ~ slf |
insulation resistance | min 20㏁ ( dc500v mega ) |
dielectric strength | ac 2000v 50/60hz for 1 minute ( between terminal and earth ) |
vibration | malfunction | 2 ~ 55hz, x,y,z each positions for 10 minutes |
durability | 10 ~ 55hz, 0.76㎜, x,y,z each positions for 2 hours |
shock | malfunction | 100㎨ 6 positions each 3 times |
durability | 300㎨ 6 positions each 3 times |
life | mechanical | min. 10 millions operations ( relay type ) |
electrical | min. 0.3 millons operations ( relay type ) |
ambient temperature and humidity | 0 ~ 50℃ ( 32 ~ 122℉ )ㆍ35 ~ 85%rh ( no icing ) |