详细介绍
德国倍加福 P+F 四通道安全栅 KFD2-SRA-EX4 信号隔离器
德国倍加福 P+F 四通道安全栅 KFD2-SRA-EX4 信号隔离器
参数表节选:的技术参数 KFD2-SRA-Ex4
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | 45 ... 70 mA | |
Power dissipation | 1.2 W | |
Input | ||
Connection | terminals 1-, 2+, 3-; 4-, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse/Pause ratio | min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation) | |
Line fault detection | breakage I ≤ 0.15 mA , short-circuit I > 6 mA | |
Output | ||
Connection | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 | |
Output I ... IV | Signal I ... Signal IV ; relay | |
Contact loading | 253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load; | |
Energized/De-energized delay | approx. 30 ms / approx. 30 ms | |
Mechanical life | 5 x 106 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | ≤ 10 Hz (non-AC operation) ≤ 3 Hz (AC operation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | ZELM 99 ATEX 0009 | |
Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Error message output | ||
Maximum safe voltage | 40 V DC | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0145 | |
IECEx approval | IECEx TUN 04.0003 | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |