Product Overview: 一、闭式冷却塔因为是全封闭式循环冷却,不存在杂物进入冷却管路体系,从而产生管路梗塞的情况;二、闭式冷却塔为软水循环冷却,在低温时也水垢产生,引起冷却管路体系结垢;三、闭式冷却塔占地面积小,不需开挖水池,易址便利,节约用水,低能耗;四、闭式冷却塔采用风冷、蒸发吸热两重冷却方法,冷却效率:五、可直接冷却水、油类,醇类、淬火液、盐水及化学液等介质,介质无消......
型号 | 流量 (m/h) | 风机 | 喷淋泵 | 配管规格(mm) | 配管规格 (mm) | 净重 Kg | ||||||
风量 (m/h) | 功率 (Kw) | 流量 (m/h) | 功率 (Kw) | 进出水口 | 补水口 | 排污口 | L | W | H | |||
MB-M6T | 30000 | 12000 | 0.75 | 20 | 0.75 | DN50 | DN20 | DN40 | 1550 | 850 | 1950 | 370 |
MB-M1OT | 50000 | 12000 | 0.75 | 20 | 0.75 | DN50 | DN20 | DN40 | 1550 | 850 | 1950 | 400 |
MB-M15T | 75000 | 12000x2 | 0.75x2 | 20 | 0.75 | DN65 | DN20 | DN40 | 2300 | 1000 | 1950 | 500 |
MB-M20T | 100000 | 12000x2 | 0.75x2 | 20 | 0.75 | DN65 | DN20 | DN40 | 2300 | 1000 | 1950 | 540 |
MB-M3OT | 150000 | 16000x2 | 1.1x2 | 45 | 1.1 | DN65 | DN20 | DN40 | 2780 | 1170 | 2380 | 710 |
MB-M40T | 200000 | 16000x2 | 1.1x2 | 45 | 1.1 | DN80 | DN20 | DN40 | 2780 | 1170 | 2380 | 775 |
MB-M5OT | 250000 | 22000x2 | 1.5x2 | 45 | 1.1 | DN80 | DN20 | DN40 | 2780 | 1300 | 2470 | 890 |
MB-M6OT | 300000 | 22000x2 | 1.5x2 | 45 | 1.1 | DN100 | DN20 | DN40 | 2780 | 1300 | 2470 | 980 |
MB-M7OT | 350000 | 22000x2 | 1.5x2 | 45 | 1.1 | DN100 | DN20 | DN40 | 2780 | 1500 | 2720 | 1140 |
MB-M8OT | 400000 | 22000x2 | 1.5x2 | 65 | 1.5 | DN100 | DN20 | DN40 | 2780 | 1500 | 2720 | 1200 |
MB-M100T | 500000 | 16000x4 | 1.1x4 | 65 | 1.5 | DN125 | DN40 | DN65 | 3200 | 2000 | 3140 | 1580 |
MB-M125T | 625000 | 16000x4 | 1.1x4 | 65 | 1.5 | DN125 | DN40 | DN65 | 3200 | 2000 | 3140 | 1750 |
MB-M150T | 750000 | 16000x6 | 1.1x6 | 120 | 2.2 | DN150 | DN40 | DN65 | 4200 | 2000 | 3150 | 2045 |
MB-M180T | 900000 | 16000x6 | 1.1x6 | 120 | 2.2 | DN150 | DN40 | DN65 | 4200 | 2000 | 3150 | 2150 |
MB-M200T | 1000000 | 16000x6 | 1.1x6 | 170 | 4 | DN200 | DN40 | DN65 | 4200 | 2000 | 3150 | 2520 |
MB-M250T | 1250000 | 75000x2 | 5.5x2 | 170 | 4 | DN200 | DN40 | DN65 | 5100 | 2300 | 4380 | 3080 |
MB-M300T | 1500000 | 100000x2 | 5.5x2 | 233 | 5.5 | DN250 | DN40 | DN65 | 5100 | 2300 | 4380 | 4050 |
MB-M400T | 2000000 | 125000x2 | 11x2 | 285 | 7.5 | DN250 | DN40 | DN65 | 5100 | 2300 | 4380 | 5700 |
MB-M500T | 2500000 | 100000x3 | 7.5x3 | 285 | 7.5 | DN300 | DN40 | DN65 | 6700 | 2500 | 4980 | 6500 |
注:
1、MB-逆流式闭式冷却塔设计工况为:干球温度31.5C、湿球温度27C、 进水温度37C、出水温度32C、大气压力99 4Kpa.
2、客户在冷却塔管道安装过程中,需在进水口处增加Y型过滤器、阀门机压力表等辅助管件。
3、噪音测试点为国家标准GB7190.1-2008中第二点(塔进风口方向离塔壁水平距为塔直径的1倍,离地1 .5米)。
4、直径2400mm以下风机标配为直传电机,选配减速器,挂号内为减速器电动机功率。
MY-C系列逆流圆塔外形示意图