ADV557-S50数字量输出模块
ADV161-S60/D6A00 ADV551-S60/D5A00 ADR541-S60/C4S70 ADV557-S60/D5A00
ADV161-PE0/D6A00 ADV551-PE0/D5A00 ADR541-PE0/C4S70 ADV557-PE0/D5A00
ADV161-SF0/D6A00 ADV551-SF0/D5A00 ADR541-SF0/C4S70 ADV557-SF0/D5A00
ADV161-P00/D6A00 ADV551-P00/D5A00 ADR541-P00/C4S70 ADV557-P00/D5A00
ADV161-S00/D6A00 ADV551-S00/D5A00 ADR541-S00/C4S70 ADV557-S00/D5A00
ADV161-P10/D6A00 ADV551-P10/D5A00 ADR541-P10/C4S70 ADV557-P10/D5A00
ADV161-S10/D6A00 ADV551-S10/D5A00 ADR541-S10/C4S70 ADV557-S10/D5A00
Item | Speci?cations | ||
Model | ADV551 | ADV557 | ADV561 |
Number of output channels | 32 | 32 | 64 |
Rated applied voltage | 24 V DC | 24 V DC | 24 V DC |
Load voltage | 24 V DC, 50 mA | 24 V DC, 50 mA | 24 V DC, 100 mA |
External power supply voltage range |
20.4 to 26.4 V DC |
20.4 to 26.4 V DC |
20.4 to 26.4 V DC |
Output ON voltage maximum value |
2 V DC |
2 V DC |
2 V DC |
Leak current maximum value when output OFF |
0.1 mA |
0.1 mA |
0.1 mA |
Output format | Current sink | Current sink | Current sink |
Maximum load current (*1) | 100 mA/channel, 26.4 V | 100 mA/channel, 26.4 V | 100 mA/channel, 26.4 V |
Withstanding voltage | Between output signal and system: 2 kV AC, For 1 minute Between commons: 500 V AC, For 1 minute, common minus (–) side every 16-channel (*2) | ||
Functions Status output Pulse width output
Time-proportioning output |
ON/OFF status output function One-shot pulse width output function Time-proportioning ON/OFF |
ON/OFF status output function —
— |
ON/OFF status output function One-shot pulse width output function Time-proportioning ON/OFF |
Output response time | 3 ms or less (for status output) 10 ms or less (for mixed status and pulse outputs) | ||
Pulse width | 8 ms to 7200 s | ||
Pulse width resolution | 8 ms, but ON/OFF delay of maximum 1 ms is added | ||
Maximum current consumption | 700 mA (5 V DC) 60 mA (external power supply) | 550 mA (5 V DC) 60 mA (external power supply) | 700 mA (5 V DC) 120 mA (external power supply) |
Weight | 0.2 kg | 0.3 kg | 0.3 kg |
External connection | Pressure clamp terminal, Dedicated cable (AKB331), MIL connector cable |
Pressure clamp terminal |
Dedicated cable (AKB337), MIL connector cable |
Digital Input Modules
The Digital Input Modules receive 32-channel or 64-channel 24 V DC ON/OFF signals. The ADV151 and ADV161 can be used in dual redundant con?guration.
Item | Speci?cations | ||
Model | ADV151-P/ADV151-E (*1) | ADV157 | ADV161 |
Number of input channels | 32 | 32 | 64 |
Rated input voltage (*2) | 24 V DC (sink/source) | 24 V DC (sink/source) | 24 V DC (sink/source) |
Input ON voltage | 18 to 26.4 V DC | 18 to 26.4 V DC | 20 to 26.4 V DC |
Input OFF voltage | 5.0 V DC or less | 5.0 V DC or less | 5.0 V DC or less |
Input current (at rated input voltage) | 4.1 mA±20 % / channel | 4.1 mA±20 % / channel | 2.5 mA±20 % / channel |
Maximum allowable input voltage | 30.0 V DC | 30.0 V DC | 30.0 V DC |
Withstanding voltage | Between input signal and system: 2 kV AC, For 1 minute Between commons: 500 V AC, For 1 minute, common every 16-channel (*3) | ||
Functions Status input
Pushbutton input |
Function for detecting ON/OFF status Function for counting the pushbutton edges |
Function for detecting ON/OFF status — |
Function for detecting ON/OFF status Function for counting the pushbutton edges |
Input response time | 8 ms or less (for status input) | ||
Minimum ON detection time | 20 ms (for pushbutton input) | ||
Maximum ON/OFF cycle | 25 Hz (for pushbutton input) | ||
Maximum current consumption | 500 mA (5 V DC) | 350 mA (5 V DC) | 550 mA (5 V DC) |
Weight | 0.3 kg | 0.4 kg | 0.3 kg |
External connection | Pressure clamp terminal, Dedicated cable (AKB331), MIL connector cable |
Pressure clamp terminal |
Dedicated cable (AKB337), MIL connector cable |
1、 什么是DCS?
DCS是分布式控制系统的英文缩写(Distributed Control System),在国内自控行业又称之为集散控制系统。
2、 DCS有什么特点?
DCS是计算机技术、控制技术和网络技术高度结合的产物。DCS通常采用若干个控制器(过程站)对一个生产过程中的众多控制点进行控制,各控制器间通过网络连接并可进行数据交换。操作采用计算机操作站,通过网络与控制器连接,收集生产数据,传达操作指令。因此,DCS的主要特点归结为一句话就是:分散控制集中管理。
3、 DCS的结构是怎样的?
DCS的控制决策是由过程控制站完成的,所以控制程序是由过程控制站执行的。
5、 过程控制站的组成如何?
控制系统需要建立信号的输入和输出通道,这就是I/O。DCS中的I/O一般是模块化的,一个I/O模块上有一个或多个I/O通道,用来连接传感器和执行器(调节阀)。
7、 什么是I/O单元?
I/O单元与CPU是通过现场总线连接的。