Solid State Relay Boards (Voltage Output)
Models | ARS55M-1 (100 V AC) | ARS55M-2 (220 V AC) | ARS55M-3 (5 - 60 V DC) |
Usage | Solid State Relay TRIAC Output, Transistor output (Single / Dual-redundant) | ||
Contact Points | 32-point | ||
Terminals for Field Device Connection | Pressure clamp terminals Cable specifications: see the table of terminal treatment for the pressure clamp terminal signal line and power line. | ||
Modules | ADV551 (DO: 32-point) + ATD5A (Terminal block) ADV561 (DO: 64-point) (*1) | ||
Signal Cables | AKB331 (for 32-point) AKB337 (for 64-point) | ||
Output Voltage/Current Range (*2) | 24 to 140 V AC
30 mA to 2.5 A (Ambient temperature is under 20 °C) 30 mA to 2 A (at 20 to 35 °C) 30 mA to 1.5 A (at 35 to 40 °C) 30 mA to 1.3 A (at 40 to 50 °C)
Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C. | 24 to 250 V AC
30 mA to 2.5 A (Ambient temperature is under 20 °C) 30 mA to 2 A (at 20 to 35 °C) 30 mA to 1.5 A (at 35 to 40 °C) 30 mA to 1.3 A (at 40 to 50 °C)
Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C. | 5 to 60 V DC
20 mA to 2.5 A (Ambient temperature is under 20 °C) 20 mA to 2 A (at 20 to 35 °C) 20 mA to 1.3 A (at 35 to 50 °C)
Inductive load must be 1.5 A or less. |
Power Supply Voltage and Current Consumption of Internal Circuit (require external power supply) |
24 V DC Max. 0.9 A | ||
Power Supply for Field Device | - | ||
Insulation Resistance | At least 10 MΩ (500 V DC) | ||
Withstanding Voltage | Between 24 V power terminals and field device terminals: 2 kV | ||
Ambient Temperature and Humidity |
0 to 50 °C, 10 to 90 %RH | ||
Standards | Safety Standard [CSA], EMC standards [CE Marking], [C-Tick Marking] , [KC Marking] | ||
Size | W: 436 mm x H: 125.4 mm | ||
Weight | 3.0 kg |