您现在的位置:智能制造网>技术首页>

基于VB的台达PLC与监控计算机的串行通信实现

2006年08月04日 09:33来源:烟台勾股通信技术有限公司 >>进入该公司展台人气:682

Implementation of Serial Communication Between Monitoring Computer and Delta PLC Based on Visual Basic
Wang Naiquan

摘要:PLC直接与现场控制层的检测仪器仪表设备连接,是底层控制网络的组成部分,是工厂自动化系统的基石,因此实现与监控层计算机的通信对系统的优化运行有重要意义。文章基于VB讨论台达DVP PLC与监控计算机的通信问题。

关键词:VB 通信协议 可编程控制器
Abstract: The PLC is a composing part of Infranet, it links to the measuring instrument and device in field control layer directly, and is the footstone of factory automation system. Therefore it is very important to realize the communication between PLC and monitoring layer computer for optimization of syste running. The paper discussed the related communication problems between Delta DVP PLC and monitoring computer based on Visual Basic.
Key Words: Visual Basic Communication protocal Programable logic controller

[中图分类号] TP273 [文献标识码] B 文章编号

1 引 言
现场设备层中的设备种类繁多,有传感器、启动器、驱动器、I/O部件、变送器、阀门等等,当然也包括现场检测仪器仪表设备。PLC是现场设备控制层*的部分,已经非常普及,如何简便地实现与PLC的交互已经成为众多厂商新的竞争战场。由此产生了人机界面等软件产品,这些产品的出现简化了对PLC的控制、操作,使PLC的应用更加方便;但也有其共同的缺点,价格普遍偏高和可二开发性较差。VB作为“原始”的编程语言在这两方面无疑有着明显优势的,本文结合一个简单的案例,用比较基础的概念讨论如何通过VB实现PC与PLC之间的通信问题,这对刚涉步控制领域的工程师或许是有帮助的。在现场设备层中各式各样的设备都可以和计算机联机,而zui简单的自动化联机方式就是使用串行通信,VB提供了串行通信控件可以让开发出串行通信的系统程序,以下是对相关问题的粗略讨论。

2 串行通信基本概念
数据通讯中有两种类型的通信形式,即并行通信(Parallel Communication)和串行通信(Serial Communication)。例如,如果有8位数据需要传送,那么并行通信一次就可以完成8位的传输量;而串行一次只能传送1位。图1表示了两种不同的通信模式,常用的串行通信也有两种,分别为RS-232和RS-485。


2.1 RS-232 串行通信
RS-232的信号准位是参考地线而言的,如图2所示。相对于参考接地端1传输端传送数据;接收端则相对于参考接地端2复现出传送端的传送的数据。
2.2 RS-485串行通信
RS-485的信号被传送出去时会分成正负两条线路,当到达接收端后,在将信号相减还原成原来的信号;如果将原始的信号表示成(DT),而被分成的信号分别标示成(D+)及(D-),则DT=(D+)-(D-)。同理,接收端在接收到信号后,也依据上式还原成原来的样子。如果线路受到干扰,两条线路的信号分别为(D+)+Noise与(D-)+Noise。接收端还原信号为(DT)= [(D+)+Noise]-[(D-)+Noise],与先前结果一样,所以RS-485可以有效的防止噪声的干扰。

3 VB的基本概念
VB(Visual Basic)是微软的窗口软件,提供了很多接口成员,对象、属性、事件、方法就是4个重要的接口,VB提供了许多常用的控件。
3.1卷标控件
3.2 按钮控件
3.3 定时器控件
VB提供了大量的控件,在此不再多述。
4 基于MScomm控件的串行通信
要完成VB与PLC等设备的串行通信要用到MScomm控件, 在此有必要对该控件作较详细的说明。Mscomm是一个非标准控件,需要要手动添加许多项目,其步骤如下。
1) 选择菜单的【工程】
2) 选择【部件】
4.1 MODBUS ASCII
Modbus 分为ASCII和RTU两种,ASCII采用的格式和校验相对简单,本文采用ASCII格式,并仅对使用的功能码进行说明,更多的信息,请参看协议的详细说明。
1)通信格式
LRC算法:ADR H+CMD H+DATA H,然后取2的补码。
2)功能码
05,写入线圈
01,读线圈状态
06,写入单个字寄存器
4.2 VB与PLC通信的实现
以下举例说明现场设备与PLC通信的实现。
1)控制要求:控制PLC的起动、停止,并显示运行状态(绿色为运行,红色为停止);能够用交替型按钮控制Y0,Y1,并用指示灯显示Y0,Y1状态(绿色为运行,红色为停止);能够对D256,D512两个寄存器进行数值写入的操作。
2)实现思路:PLC起动停止的标志位为M1072,查DVP协议,知道地址为H0C30,按功能码01操作; 同样Y0,Y1的地址分别为H0500,H0501。写入FF00为ON,0000为OFF,按功能码05操作;D256,D512地址分别为H1100,H1200,按功能码06操作即可。
3)VB接口
用按钮控制PLC的起动停止,Y0、Y1的ON/OFF及D256、D512写完数据的发送;用Shape组件做指示灯,表示PLC的运行状态和Y的状态;用timer组件不停的读取M1072的状态,以判断PLC的运行情况;用MScomm控件实现PC与PLC的通信。
4)编程实现的代码构成
(1) LRC算法校验的实现
Public Function LRC(str As String) As String
c = 0
l = Len(str)
For c = c + 1 To l
c_data = Mid$(str, c, 2)
d_lrc = d_lrc + Val("&H" + c_data)
c = c + 1
Next c
If d_lrc > &HFF Then
d_lrc = d_lrc Mod &H100
End If
h_lrc = Hex(&HFF - d_lrc + 1)
If Len(h_lrc) > 2 Then
h_lrc = Mid(h_lrc, Len(h_lrc) - 1, 2)
End If
LRC = h_lrc
End Function
(2) 运行的开始就判断PLC的状态并设置标志位
'初次运行打开串口,并显示PLC运行状态
Private Sub Form_Load()
Dim s1 As String
Dim s2 As String
Dim s22 As String
Dim s3 As String
Dim s4 As String
MSComm1.PortOpen = True
s2 = "01010C300001"
s22 = LRC(s2)
s1 = ":" + s2 + s22 + Chr$(13) + Chr$(10)
MSComm1.Output = s1
s3 = MSComm1.Input
s4 = Mid$(s, 6, 8)
If s4 = "0C30FF00" Then
plc = 1 'PLC为运行标志
Else
plc = 0 'PLC为停止标志
End If
End Sub
(3) 下面一段为用指示灯表示PLC的运行状态
Private Sub Timer5_Timer()
Dim s1 As String
Dim s2 As String
Dim s22
Dim s3 As String
Dim s4 As String
s2 = "01010C300001"
s22 = LRC(s2)
s1 = ":" + s2 + s22 + Chr$(13) + Chr$(10)
MSComm1.Output = s1
s3 = MSComm1.Input
s4 = Mid$(s3, 8, 2)
If s4 = "31" Then
plc = 1 'PLC为运行标志
Else: If s4 = "30" Then plc = 0 'PLC为停止标志
End If
If plc = 1 Then
Label2.Caption = "PLC正在运行......"
Shape1.FillColor = RGB(0, 255, 0) 'green
Else
Label2.Caption = "PLC已经停止"
Shape1.FillColor = RGB(255, 0, 0) 'red
End If
End Sub
(4) PLC的起动与停止
'起动PLC
Private Sub start_Click()
Dim strout As String
Timer5.Enabled = False
str = "00050C30FF00" 'M1072 为PLC起动停止标志位。查地址表,M1072为OC30.FF00为置
ON,0000为置OFF。
'以上都是固定格式,要牢记。
LRCC = LRC(str) '计算 str的lrc校验码。
strout = ":" + str + LRCC + Chr$(13) + Chr$(10) '欲传送之数据。13为D,10为A
MSComm1.Output = strout
Timer5.Enabled = True
End Sub
'停止PLC
Private Sub stop_Click()
Dim strout As String
Timer5.Enabled = False
str = "00050C300000"
LRCC = LRC(str)
strout = ":" + str + LRCC + Chr$(13) + Chr$(10)
MSComm1.Output = strout
Timer5.Enabled = True
End Sub
Y0、Y1的ON/OFF与PLC起动/停止的控制方式相同,指示灯的表示方式也相同。D256,D512数据写入的操作类似,限于篇幅其它代码就不再列出了。

5 结束语
VB语言易于编程使用,为与串行设备的通信提供了很大的方便。台达PLC采用标准的目前广为流行的MODBUS协议,为实现PLC与监控计算机的通信提供了简化的平台。由于台达所有的机电产品都支持MODBUS协议,所以,掌握了VB与PLC通信过程,也就等于掌握了PC与台达所有机电产品的通信。
作者简介
王乃全(1978-),男,自动化设备工程师,主要从事PLC控制系统的开发与。
全年征稿/资讯合作 联系邮箱:1271141964@qq.com
  • 凡本网注明"来源:智能制造网"的所有作品,版权均属于智能制造网,转载请必须注明智能制造网,https://www.gkzhan.com。违反者本网将追究相关法律责任。
  • 企业发布的公司新闻、技术文章、资料下载等内容,如涉及侵权、违规遭投诉的,一律由发布企业自行承担责任,本网有权删除内容并追溯责任。
  • 本网转载并注明自其它来源的作品,目的在于传递更多信息,并不代表本网赞同其观点或证实其内容的真实性,不承担此类作品侵权行为的直接责任及连带责任。其他媒体、网站或个人从本网转载时,必须保留本网注明的作品来源,并自负版权等法律责任。
  • 如涉及作品内容、版权等问题,请在作品发表之日起一周内与本网联系,否则视为放弃相关权利。


编辑精选

更多


宣传样本推荐图书

旗下子站

工控网机器人仪器仪表物联网3D打印工业软件金属加工机械包装机械印刷机械农业机械食品加工设备制药设备仓储物流环保设备造纸机械工程机械纺织机械化工设备电子加工设备水泥设备海洋水利装备矿冶设备新能源设备服装机械印染机械制鞋机械玻璃机械陶瓷设备橡塑设备船舶设备电子元器件电气设备



关于我们|本站服务|会员服务|企业建站|旗下网站|友情链接| 兴旺通| 产品分类浏览|产品sitemap

智能制造网 - 工业4.0时代智能制造领域“互联网+”服务平台

Copyright gkzhan.comAll Rights Reserved法律顾问:浙江天册律师事务所 贾熙明律师

客服热线:0571-87756395加盟热线:0571-87759904媒体合作:0571-89719789

客服部:编辑部:展会合作:市场部:

关闭