HDL6智能综合漏电保护器
![](https://img79.gkzhan.com/bb33f2c9b6dc3b85446c3d68e78026079aeec9e2a9ee5ff429053951fccb7443e2c7884d681a4765.jpg)
![](https://img79.gkzhan.com/bb33f2c9b6dc3b85446c3d68e7802607fa16c516af10a9a48cc15859e5ac78e6c105b06d9ad8e75e.jpg)
![](https://img79.gkzhan.com/bb33f2c9b6dc3b85446c3d68e780260705e9d807d81724b2ed44a985e482c95a580bf8869646eb1d.jpg)
周围 空气湿度 +30℃±2℃ | 试验电流 | 脱扣时间 | 状态 |
1.05In | 2h不脱扣 | 冷态开始 | |
1.30In | 2h内脱扣 | 热态开始 | |
3In | 可返回>2S | 冷态开始 | |
任何湿度 | 10In | <0.2S | 冷态开始 |
+20℃±2℃ | 1.05In | 2h不脱扣 | 冷态开始 |
1.30In | 2h内脱扣 | 热态开始 |
缓变突变电流动作值设置 | ||||||
开关位置ON=1 | 突变电流 mA | 缓变电流 mA | 分断时间 | |||
1 | 2 | 3 | 4 | |||
0 | 0 | 0 | 0 | 50 | 300 | 0.2 |
1 | 0 | 0 | 0 | 75 | 300 | 0.2 |
0 | 1 | 0 | 0 | 100 | 300 | 0.2 |
1 | 1 | 0 | 0 | 50 | 500 | 0.2 |
0 | 0 | 1 | 0 | 75 | 500 | 0.2 |
1 | 0 | 1 | 0 | 100 | 500 | 0.2 |
0 | 1 | 1 | 0 | 50 | 800 | 0.5 |
1 | 1 | 1 | 0 | 75 | 800 | 0.5 |
0 | 0 | 0 | 1 | 100 | 800 | 0.5 |
1 | 0 | 0 | 1 | 无 | 300 | 0.1 |
0 | 1 | 0 | 1 | 无 | 500 | 0.1 |
1 | 1 | 0 | 1 | 无 | 800 | 0.1 |
0 | 0 | 1 | 1 | 显示三相漏电和 | ||
0 | 1 | 1 | 1 | 显示A相当前漏电值 | ||
1 | 1 | 1 | 1 | 显示B相当前漏电值 | ||
1 | 0 | 1 | 1 | 显示C相当前漏电值 |